How to Test Electrical Ring Main Circuits

The UK was the first and is now is probably the only country in the world which still uses the 30 amp ring system for wiring socket outlets in electrical installations. The ring main circuit has long been the subject of many a heated discussion between electrical experts, but as an electrician you'll no doubt need to test them in the course of your duties. Here is an overview of Ring Main inspection and testing procedures.

Warning- Please note that this is a 'dead' test so the distribution board, consumer unit or circuit must be isolated from the electrical supply. To begin with you'll need to carry out a Safe Isolation Procedure and get permission to turn off the supply.

Here's the testing procedure:

Insulation Resistance

Disconnect all appliances and accessories from the ring circuit and carry out insulation tests between the Line, Neutral and Earth CPC.

End to End Ring Continuity Test

Set your test meter to low resistance range and 'zero' the test leads. Measure the resistance of ring continuity of each of the live, neutral and earth conductor ring loops. Record these end to end readings for future reference and entering onto a test sheet. Note that where the earth conductors are smaller, the resistance will obviously be higher. For example for twin and earth cables 1.5mm will be 1.66 times higher than 2.5mm.

Super Loop Test L&N

Cross connect the live and neutral conductors from opposite ends of the ring and to form a super loop. If at first this sounds confusing, try drawing the live and neutral loops of a ring circuit on a piece of paper with the opposite ends connected. You'll see that it forms one big super loop.

Test resistance between the ends you have just connected together. The reading taken between the super loop ends should be about half that of your previous continuity reading. You can then verify the ring main wiring and connections by going to each socket outlet and testing between live and neutral. Where the socket is on the ring and the connections are 'good', your readings should be within 0.05 of your original super loop reading at the distribution board.

These readings are not normally recorded but will form the basis for your assessment of the ring main circuit connections.

High readings could indicate that the socket is on a spur from the ring, that connections need tightening or that the socket is faulty giving a poor connection to the plug and needs replacing. Where the readings are not consistent this could indicate that there are cross connections and the ring circuit has been bridged.

Super Loop Test L&E

Cross connect the line and earth conductors from opposite ends of the ring and to form a super loop. Test between the two sets of ends you have just connected together. The resistance reading should be about half that of your previous continuity reading. You can then verify the ring main wiring and connections by measuring the resistance at each socket outlet as for Live and Neutral described previously. Testing between live and earth at the sockets also checks for correct polarity.









0 comments

  • Equating Profitability With Cashflows: A Myth in Corporate Financial Performance The issue of profit and cashflow and their relative importance in business has become an unending discussion in recent boardroom discussions. As some analyst are looking at profit history of business to assess performance, others are looking at…
  • Prediction of Sudden Gains and Unexpected Prosperity in Astrology In today's world, most of the people wish to earn a lot of wealth and prosperity in their life, for fulfillment of their desires. Sometimes they choose risky steps to gain sudden benefits and prosperity. Lottery, shares, gambling,…
  • How To Saving Money Building Custom Homes Designing a new house is exciting as endless creative ideas can be transformed into a reality, however being mindful of a budget can save unnecessary expenses and much heartache down the line. Constructing houses from the ground up involves…
  • Freight Management Solutions Business models of all sizes have complications. The goal of businesses in terms of logistics basically narrows down to having what the consumer desires, at a price they are willing to pay, in the quantity they wish for when they want it. That…
  • Wind Deflectors - Lessen Your Car's Fuel Consumption Wind deflectors are accessories for cars that you would normally find on the hood, sunroof and side windows. Deflectors mounted on the front hood of a car will give protection to the vehicle from any debris that may be thrown up into its path by…